     Most people are familiar with how a regular 120 volt circuit is constructed (a hot, a neutral and a grounding conductor). Some may even understand how a 240 volt circuit operates (two hots, a neutral and a grounding conductor).  But what the heck is a multi-wire branch circuit? Well, a multi-wire branch circuit is kind of a cross between a 240 volt circuit and a 120 volt circuit.  It uses a 240 volt cable but it’s wired for essentially two 120 volt circuits.  A multi-wire branch circuit is a branch circuit with at least two circuit phase conductors having a voltage between them, with equal voltage between each phase conductor and the neutral conductor.  Let’s take a look at the diagram below. 

Picture shows how a multi-wire branch circuit works.
How a multi-wire branch circuit works.

Multi-Wire Branch Circuit Requirements

A multi-wire branch circuit must-

  • All conductors of a  multi-wire branch circuit must originate from the same panelboard.
  • Each multi-wire branch circuit shall be provided with a means to simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.
  • A multi-wire branch circuit shall supply only line to neutral loads. (some exceptions apply)
  • The ungrounded and grounded conductors shall be grouped by wire ties or similar means in at least one location in the panelboard.
  • Continuity of neutral must not depend on the connection to a device such as a receptacle.
  • See NEC 210.4 for more info.
Example of a multi-wire branch circuit.
Example of how a multi-wire branch circuit is wired.

Advantages of a Multi-Wire Branch Circuit

Below are some advantages of this type of circuit.

  • Less expensive because fewer conductors are needed (less copper).
  • Less labor because there are fewer wires to pull.
  • Takes up less space in panelboards and raceways.
  • Less (a lot less) voltage drop across a distance.
  • Greater flexibility and capacity. You’re essentially getting two circuits instead of just one. This can be handy in some wiring situations (like wiring a detached shed for instance).

Disadvantages of a Multi-Wire Branch Circuit

Multi-wire branch circuits are safe if installed correctly however there are some things to watch out for.

  • Connections need to be secure and tight.  A loose neutral for instance anywhere in the circuit can cause an over-voltage condition on one side and an under voltage condition on the other side of the circuits.  This could destroy delicate electronic equipment for instance or cause a fire.  A loose neutral can happen many years after original construction during routine maintenance repairs like changing out a receptacle for instance.
  • A multi-wire circuit works best when the loads are balanced because there’s less return current on the neutral.  Though this is not a defect it’s something to consider during installation.
  • In some cases a multiwire branch circuit causes issues with arc-fault and GFCI breaker types.
  • Installation Errors- Common installation errors include not using a handle tie, using separate breakers on each side of the panel,  wiring it through a device,  or not making sure the breakers are on opposite phases.  This last one is a potential fire hazard because it would tend to overload the neutral.

Blue Palmetto Home Inspection Serves Summville SC and surrounding areas.  Call us today! 843-934-3045